For Galil controllers with internal amplifiers (AMP/SDM options), the IOC monitors amplifier health. Status is derived from the Galil TA (Tell Amplifier error status) command bits, parsed from the data record.

Quad Amplifier Status

Template: galil_quadAmpStatus.template

PV pattern: $(P)$(AMP)_ where AMP is the amplifier bank name. ADDR maps to the amplifier bank.

PV Suffix Record Type asyn drvInfo Galil Cmd Description
_OVERCURRENT_STATUS bi AMP_OVERCURRENT_STATUS TA bit, data record Overcurrent fault (MAJOR alarm)
_UNDERVOLTAGE_STATUS bi AMP_UNDERVOLTAGE_STATUS TA bit, data record Undervoltage fault (MAJOR alarm)
_OVERVOLTAGE_STATUS bi AMP_OVERVOLTAGE_STATUS TA bit, data record Overvoltage fault (MAJOR alarm)
_OVERTEMPERATURE_STATUS bi AMP_OVERTEMPERATURE_STATUS TA bit, data record Overtemperature fault (MAJOR alarm)
_ELO_STATUS bi AMP_ELO_STATUS TA bit, data record Electronic lockout active (MAJOR alarm)

All status PVs use I/O Intr scanning and transition to MAJOR alarm severity on fault. To clear latched faults, use the controller-level CLEARAMPFAULTS_CMD PV, which issues the Galil AZ (Clear Latched Amplifier Errors) command.